• 11151 Amman, Jordan

Miniature Circuit Breakers: 10kA 80A to 125AHti

The miniature circuit breakers of the Series Hti are the biggest breakers within our range of MCB’s (210 g/pole). They are meant to be used for heavier applications, their nominal current goes upto 125A and they have a calibration temperature of 40°C (for the other MCB’s within our range this is 30°C, except for the Series GT).

This is also reflected in the terminal capacity for rigid cables, 70mm 2 , while for other miniature circuit breakers this is maximum 16 (C-series) or 35mm 2.

Following add-on devices are available for this product: auxiliary contacts, shunt trip (Tele L) and panel board switch (PBS).

No accessories are available for the Series Hti.

See below the main features for this range.

Features / Producttypes Hti
Standards EN/IEC 60947-2
Short circuit breaking capacity (Acc.to EN/IEC 60947-2, curves B,C) (kA) 10, 15
Tripping characteristics B, C, D
Thermal settings ln (A) 80-100-125
Rated voltage AC Un (V) 230/400
Minimum operating voltage U B min (V) 12
Selectivity class
Mechanical/electrical endurance 10000/4000
Tropicalisation acc.to EN/IEC 60068-2 95%RH at 55°C
Terminal capacity flexible/rigid cable (mm 2 ) 70
Poles 1
  2
  3
  4
Weight (g/pole) 210
CE-marking X
Auxiliary contacts yes
Tele U (Undervoltage release)
Tele L (Shunt Trip) yes
Tele MP (Motor Operator)
PBS (Panel board switch) yes
Busbar system pin (top/bottom)
Busbar system fork (top/bottom)
Accessories
Read More

Miniature circuit breakers for photovoltaic applications

First solution for growing market of solar electric power.

  • Compact design
  • High voltage 880V upto 63A
  • Safetylock with padlocking bracket
  • Add-on devices for remote signalisation and tripping
  • Add-on motor driver Tele MP

 

Features / Producttypes EP 100UC EP 104UC
Curve B B
Thermal setting In (A) 6-63 10-63
Rated voltage DC Un (V) 440 880
Maximum operating voltage DC (V) 250 1000
Minimum operating voltage DC (V) 12 12
As loadbreak disconnector yes yes
Rated insulation voltage Ui, pollution degree 2 (V) 500 1200
Rated insulation voltage Ui, pollution degree 3 (V) 440 1000
Rated impulse withstand voltage Uimp (kV) 6 6
Dielectric rigidity (kV) 2,5 2,5
Mechanical/electrical endurance 20.000/1.000 ops. 20.000/1.000 ops.
Poles 2 4
Modules 2 4
Read More

Miniature Circuit Breakers:MCB’s with UL approval

Below you can find our miniature circuit breakers with UL approval. A product that has the approval of Underwriters Laboratories (UL) has met all of UL’s safety requirements. Products that pass the muster of this company get the UL symbol of approval.
Underwriters Laboratories (UL) is one of the world’s leading providers of product safety and certification testing services, performing more than 100,000 product evaluations each year. Products that pass its stringent tests become registered with the company and can bear the UL Mark, which has become a widely trusted symbol for product safety and assurance. Nearly 20 billion products from 70,000 manufacturers bear the UL Mark.

Our MCB’s with UL approval can be delivered with following add-on devices:
Auxiliary contacts, shunt trip (Tele L) and motor operator (Tele Mp).
Accessories are available for the EP60 UL and the EP100UL.
See below the main features for this range.

Features / Producttypes EP60 UL EP100 UL EP100 ULH
Standards EN/IEC 60898-1 EN/IEC 60898-1
  EN/IEC 60947-2 EN/IEC 60947-2
  EN 60947-2
UL approval UL 1077 UL 1077 UL 489
UL-file E151139 E151139 E256870
Short circuit breaking capacity (kA) (AC, 60898) 6 10
Tripping characteristics B, C, D
Thermal settings ln (A) 0,5-63 0,5-63 0,5-32
Rated voltage AC Un ~ (V) 277/480 277/480 120/240
Rated voltage AC Un = (V) 110
Minimum operating voltage U B min (V) 12
Selectivity class 3
Mechanical/electrical endurance 20000/10000
Tropicalisation acc.to IEC 60068-2-28/2-30 95%RH at 55°C
Terminal capacity flexible/rigid cable (mm 2 ) 25-35
Poles 1 1 1
  2 2 2
  3 3 3
  4 4
Weight (g/pole) 125 125 130
CE-marking X
UR X X
CSA, CEC X X
VDE X X
NEC, OSHA X
Auxiliary contacts yes
Tele U (Undervoltage release)
Tele L (Shunt Trip) yes
Tele MP (Motor Operator) yes
PBS (Panel board switch)
Busbar system pin (top/bottom)
Busbar system fork (top/bottom)
Accessories
Read More

Miniature Circuit Breakers: Series EP

Below you can find four of our types out of the Series EP.
The EP60 and EP100 are the most commonly used MCB’s in the range of our residential circuit breakers. The EP60 and EP100 are simular to the G60 and G100. However, the G-types are available with the tripping curves B-C-D,while the EP60 and EP 100 only use the K-curve. There is no 1+N execution in the K-curve. A second difference is that the MCB’s within the Series EP have a labelholder, so they can be tagged. For the Series G this is not the case.
The EP100 UC breaker can be used for direct and alternating current.
The EP100 R is used for railway applications.
Our MCB’s within the Series EP can be delivered with following add-on devices:
Auxiliary contacts, undervoltage release (Tele U), shunt trip (Tele L), motor operator (Tele Mp) and panel board switch (PBS).
Accessories are available for the MCB’s within our Series EP.

It also needs to be mentioned that this is not the complete Series EP. We also offer EP-breakers with UL approval. For more details you should go to the Series EP with UL approval page of our website..

See below the main features for this range.

Features / Producttypes EP60 EP100 EP100 UC EP100 R
Standards EN/IEC 60898-1 EN/IEC 60898-1
  EN/IEC 60947-2 EN/IEC 60947-2 EN/IEC 60947-2
  EN/IEC 60898-2
  DIN VDE 0641
  EN 60898
  EN 60947-2
Short circuit breaking capacity (kA) (AC, 60898) 6 10 6 10
Tripping characteristics 8-12 ln (K) and 6 in non tripping ≤ 2 sec. 8-12 ln (K) and 6 in non tripping ≤ 2 sec. B, C B, C
Thermal settings ln (A) 2-63 0,5-63 0,5-63 0,5-63
Rated voltage AC Un ~ (V) 240/415 240/415 230/400 230/400
Rated voltage AC Un = (V) 220/440
Minimum operating voltage U B min ~ (V) 12
Minimum operating voltage U B min = (V) 12
Selectivity class 3
Mechanical/electrical endurance 20000/10000
Tropicalisation acc.to EN/IEC 60068-2 95%RH at 55°C 95%RH at 55°C 95%RH at 55°C
Tropicalisation acc.to IEC 60068-2-28/2-30 95%RH at 55°C
Terminal capacity flexible/rigid cable (mm 2 ) 25-35
Poles 1 1 1
  2 2 2
  3 3 3
  4 4
Weight (g/pole) 120 120 120 125
CE-marking X
Bombardier Transportation Approval (EN 50155) X
Auxiliary contacts yes
Tele U (Undervoltage release) yes
Tele L (Shunt Trip) yes
Tele MP (Motor Operator) yes
PBS (Panel board switch) yes
Busbar system pin (top/bottom) yes/yes
Busbar system fork (top/bottom) -/yes yes/yes
Accessories yes
Read More

Modular Control Devices – Galax – LightSensitive Switches

Easy to use timer to control lighting in shops, offices, car parks, advertising signs or even in the home via a photo cell to switch on/off a light when the light intensity drops below a programmed level.

  • In accordance with BSEN60669-1, VDE0633
  • Lux settings between 5-500
  • 1 or 2 c/o contact options
  • Nominal current 16A/250V
  • 1 or 3 modules or wall mounting version
  • Operating voltage 230V
  • DIN rail mounting or wall mounting
  • Surface mounting enclosure available for DIN rail mounted version
Read More

Miniature Circuit Breakers: Series GT

The Series GT miniature circuit breakers have a calibration temperature of 40°C. This differentiates them from the other Series G (30°C).
Within this series the GT10 has a smaller short circuit capacity than the GT25.
Following add-on devices can be delivered with these products: Auxiliary contacts, undervoltage release (Tele U), shunt trip (Tele L), motor operator (Tele Mp) and panel board switch (PBS).
Accessories are available for the MCB’s within our Series GT.
See below the main features for this range.

Features / Producttypes GT10 GT25
Standards EN/IEC 60947-2
Short circuit breaking capacity (kA) (AC) 10-30 15-100
Tripping characteristics B, C, D
Thermal settings ln (A) 0,5-63
Rated voltage AC Un (V) 240/415
Minimum operating voltage U B min (V) 12
Selectivity class
Mechanical/electrical endurance 20000/10000
Tropicalisation acc.to EN/IEC 60068-2 95%RH at 55°C
Terminal capacity flexible/rigid cable (mm 2 ) 25-35
Poles 1
  2
  3
  4
Weight (g/pole) 120
CE-marking X
Auxiliary contacts yes
Tele U (Undervoltage release) yes
Tele L (Shunt Trip) yes
Tele MP (Motor Operator) yes
PBS (Panel board switch) yes
Busbar system pin (top/bottom) yes/yes
Busbar system fork (top/bottom) -/yes
Accessories yes
Read More

Modular Control Devices – 72×72 Classic andGalax Time Switches

Going from the pre-programmed switching of lighting (car parks, public roads, et.) over pre-programmed switching of heating equipment (homes and offices) to the pre-programmed switching of motors for pumps and fans.

Very easy programming by means of mechanical switches or digital buttons.

  • day program, week program and day/week program
  • 4 Modules
  • Nominal current : 16/250V
  • Operating voltage : 220-240VAC
Read More

Miniature Circuit Breakers: Series G

The Series G miniature circuit breakers are covering a complete range of short circuit breaking capacities and tripping characteristics.
Our MCB’s within the Series G can be delivered with add-on devices:
Auxiliary contacts, undervoltage release (Tele U), shunt trip (Tele L), motor operator (Tele Mp) and panel board switch (PBS) (exception: G20).
Accessories are available for the MCB’s within our Series G, except for the G20.
The S-types are especially meant for shipping applications (G60 S and G100 S).
See below the main features for this range

Features / Producttypes G20 G30 G45 G60 G60 S G100 G100 S
Standards EN/IEC 60898-1 EN/IEC 60898-1 EN/IEC 60898-1 EN/IEC 60898-1 EN/IEC 60898-1
  EN/IEC 60947-2 EN/IEC 60947-2 EN/IEC 60947-2 EN/IEC 60947-2
  EN 60898 EN 60898
  EN 60947-2 EN 60947-2
Short circuit breaking capacity (kA) (AC, 60898) 3 3 4.5 6 6 10 10
Tripping characteristics C B, C B, C B, C, D B, C, D B, C, D B, C, D
Thermal settings ln (A) 6-40 2-40 2-40 0,5-63 0,5-63 0,5-63 0,5-63
Rated voltage

AC Un (V)
240/415 240/415 240/415 240/415 230/400 240/415 230/400
Minimum operating voltage U B min (V) 12
Selectivity class 3 3 3 3 3 3
Mechanical/ electrical endurance 20000/10000
Tropicalisation acc.to EN/IEC 60068-2 95%RH at 55°C 95%RH at 55°C 95%RH at 55°C 95%RH at 55°C 95%RH at 55°C
Tropicalisation acc.to IEC 60068-2-28/2-30 95%RH at 55°C 95%RH at 55°C
Terminal capacity flexible/rigid cable (mm 2 ) 25-35
Poles 1 1 1 1 1 1 1
  1+N 1+N
  2 2 2 2 2 2 2
  3 3 3 3 3 3 3
  4 4 4 4 4 4 4
Weight (g/pole) 120 120 120 120 125 120 125
CE-marking X
KEMA X X X X
CEBEC X X
Lloyd’s register of shipping X X
Auxiliary contacts yes
Tele U (Undervoltage release) yes
Tele L (Shunt Trip) yes
Tele MP (Motor Operator) yes
PBS (Panel board switch) yes
Busbar system pin (top/bottom) yes/yes
Busbar system fork (top/bottom) -/yes
Accessories yes
Read More