• 11151 Amman, Jordan

Miniature Circuit Breakers: Series EP

Below you can find four of our types out of the Series EP.
The EP60 and EP100 are the most commonly used MCB’s in the range of our residential circuit breakers. The EP60 and EP100 are simular to the G60 and G100. However, the G-types are available with the tripping curves B-C-D,while the EP60 and EP 100 only use the K-curve. There is no 1+N execution in the K-curve. A second difference is that the MCB’s within the Series EP have a labelholder, so they can be tagged. For the Series G this is not the case.
The EP100 UC breaker can be used for direct and alternating current.
The EP100 R is used for railway applications.
Our MCB’s within the Series EP can be delivered with following add-on devices:
Auxiliary contacts, undervoltage release (Tele U), shunt trip (Tele L), motor operator (Tele Mp) and panel board switch (PBS).
Accessories are available for the MCB’s within our Series EP.

It also needs to be mentioned that this is not the complete Series EP. We also offer EP-breakers with UL approval. For more details you should go to the Series EP with UL approval page of our website..

See below the main features for this range.

Features / Producttypes EP60 EP100 EP100 UC EP100 R
Standards EN/IEC 60898-1 EN/IEC 60898-1
  EN/IEC 60947-2 EN/IEC 60947-2 EN/IEC 60947-2
  EN/IEC 60898-2
  DIN VDE 0641
  EN 60898
  EN 60947-2
Short circuit breaking capacity (kA) (AC, 60898) 6 10 6 10
Tripping characteristics 8-12 ln (K) and 6 in non tripping ≤ 2 sec. 8-12 ln (K) and 6 in non tripping ≤ 2 sec. B, C B, C
Thermal settings ln (A) 2-63 0,5-63 0,5-63 0,5-63
Rated voltage AC Un ~ (V) 240/415 240/415 230/400 230/400
Rated voltage AC Un = (V) 220/440
Minimum operating voltage U B min ~ (V) 12
Minimum operating voltage U B min = (V) 12
Selectivity class 3
Mechanical/electrical endurance 20000/10000
Tropicalisation acc.to EN/IEC 60068-2 95%RH at 55°C 95%RH at 55°C 95%RH at 55°C
Tropicalisation acc.to IEC 60068-2-28/2-30 95%RH at 55°C
Terminal capacity flexible/rigid cable (mm 2 ) 25-35
Poles 1 1 1
  2 2 2
  3 3 3
  4 4
Weight (g/pole) 120 120 120 125
CE-marking X
Bombardier Transportation Approval (EN 50155) X
Auxiliary contacts yes
Tele U (Undervoltage release) yes
Tele L (Shunt Trip) yes
Tele MP (Motor Operator) yes
PBS (Panel board switch) yes
Busbar system pin (top/bottom) yes/yes
Busbar system fork (top/bottom) -/yes yes/yes
Accessories yes
Read More

Residential Enclosures – Fix-o-Rail Junior

  • High resistance material
  • Modern design
  • Compact construction
  • High protection degree
  • IP40: 4 modules
  • IP43: 8 modules
  • Total insulation
  • Total security
  • Transparent cover allowing visibility of devices
  • For all modular equipment
  • Available in 4 and 8 modules
  • Colour: RAL 7035
  • Polystyreen for the base
  • Flame resistance: self extinguishing material, resist the 650°C
  • Polycarbonate for the lid
  • Flame resistance: self extinguishing material, resist the 960°C
Read More

VBS-Busbar system : Insulated Busbars

  • Insulated busbar, pin type system
  • Pin type for 2P or 1PN and 3P systems
  • Easy to install
  • Flat design = gain of space in the enclosure
  • Easy to use : cutting instead of sawing
  • Clear visibility when connecting the power supply cables
  • Universal for all power supplies (2 x 230V, 3 x 230V and 3 x 400 V + N)
Read More

Residential Controls Devices – Add-On RCD’s

People protection against the risk of electrocution and property protection against the risk of an electrical fire.

  • In accordance with IEC 61009
  • Unique connection system provides optimum user safety
  • For use with 2P, 3P & 4P MCB’s up to 63A (up to 125A using HTi MCB and HTi add-on RCD)
  • People protection against the risk of electrocution 10mA, 30mA and 100mA and above mainly protection against the risk of an electrical fire
  • 30mA, 100mA, 300mA, 500mA and 1000mA sensitivities
  • Available in type AC, A and S (Selective/Time delayed)
Read More

Tele REC: The Ultimate Reconnection System forRCCB’s

Ensures power continuity in critical applications.

The Tele REC relay automatically recloses the RCCB after an earth leakage or a manual disconnect. The relay will attempt to re-close 6 times with different time intervals between re-close attempts. After 6 unsuccessful attempts the Tele REC is locked.

Features

  • Status indicator: The yellow lever clearly indicates the status of the Tele REC. In position 1 the relay is ready to work, in position 0 the relay is blocked both electrically and mechanically.
  • Easy connection: The RCCB toggle slides easily into the toggle actuator of the relay.
  • Part of the family: For each series of RCCB’s – ElfaPlus, Redline and DMS line – a specific Tele REC reconnector is available.
  • Auxiliary contact: Tele REC is equipped with an auxiliary contact (LI) to operate the re-closing system from a push-button.
  • Stable and secure: Strong clips to ensure a stable connection between the RCCB and the Tele REC relay.
  • Full awareness: The relay is also equipped with a volt free output to indicate the status of the protection (connected/ disconnected).
  • One fits all: Both 2 modules and 4 modules RCCB’s can be connected to the reconnection relay Tele REC.

Complete range of reconnection relays

 

  • Tele REC DMS: Specially designed for the residential market.
  • Tele REC BASIC Type A and AC: For the residential/commercial markets. Commercial, banks, office buildings, hospitals,..
  • Tele REC BASIC Type Ai: Power maintenance and reliability in one device. Banks, hospitals, farms, public lighting, traffic lighting,…
  • Tele REC PLUS: For the commercial/industrial markets. The reconnection relay Tele REC Plus can be easily coupled to any ElfPlus RCCB.
  • Tele REC SOLAR: Specially designed for photovoltaic applications. The reconnection relay Tele REC SOLAR can be easily coupled to MCB’s series EP100 UC.

 

Read More

Residential Controls Devices -RCBO’s DME

Supplementary protection for people from the risk of electrocution and for property from the risk of an electrical fire. Overcurrent protection of equipment and cables.

  • Series DME

  • In accordance with IEC 61009
  • 6 and 10kA fault rating
  • Type AC or type A
  • Combines over current (MCB) and earth leakage (RCD) protection in one unit
  • People protection against the risk of electrocution 10mA, 30mA and 100mA and above mainly protection against the risk of an electrical fire
  • Ratings 6A, 10A, 16A, 20A, 25A, 32A, 40A
  • Type B and C tripping characteristic
  • Flying neutral lead version for installing in consumer units, and distribution boards
  • Wire in/out (not shown) for OEM / separate enclosure installation
  • 2 Module RCBO 1P+N isolates both live and neutral
  • 1 Module RCBO offers space saving features and makes upgrading circuits easy
  • 1 Module RCBO includes earth reference cable to provide protection in case of loss of neutral
Read More

Residual Current Circuit Breakers – RCBO’s DPA100 UL approval

People protection against the risk of electrocution and property protection against the risk of an electrical fire. Also with overcurrent protection.

 

  • In accordance with EN/IEC 61009-1
  • Recognized UL 1053, UL file E248309
  • Maximum voltage AC (V) 240 or 277
  • Fault current withstand (kA) 5 (277V), 10 (240V)
  • Thermal settings In (A) 10-32
  • Residual current IΔ n (mA) 10, 30, 100, 300
  • Tripping characteristic B-C
  • Selectivity class 3
  • Rated maximum voltage AC Un (V) 240
  • Minimum operating voltage U bmin (V) 100
  • Nuisance tripping resistance  250A 8/20μs;
                                                   200A 0,5μs-100kHz
  • Making and breaking capacity (EN/IEC 61009-1) Im = 6000A
  • Residual making and breaking capacity (EN/IEC 61009-1) Icn = 5000/10000A at 230V
  • Short-circuit capacity (EN/IEC 60947-2) Icu = 15000A at 230V
  • CEBEC and UR approval
Read More

Residual Current Circuit Breakers – RCCB’sseries FPAUL UL approval

People protection against the risk of electrocution and property protection against the risk of an electrical fire.

 

  • In accordance with EN/IEC 61008-1
  • Recognized UL 1053, UL file E248309
  • Maximum voltage AC (V) 240
  • Fault current withstand (kA) 10
  • Thermal settings In (A) 16, 25, 40, 63
  • Residual current IΔ n (mA) 10, 30, 100, 300, 500
  • Rated maximum voltage AC Un (V) 2P: 240,4P: 240/415
  • Minimum operating voltage U bmin (V) 2P: 117, 4P: 190
  • Type A with 2 poles and 4 poles
  • Terminal capacity flexible/rigid cable (mm 2) 35-50
  • Nuisance tripping resistance Type A: 250A 8/20μs;                                                             3000A 8/20μs
  • Making and breaking capacity Im = 500A
  • Residual making and breaking capacity
                                            IΔm ≥ 500A from 16 up to 40A                                         IΔm  = 10In from 63 up to 100A
  • Short-circuit capacity Inc =
    10000A at 230/400V fuse 80A gG
  • UR approval
Read More