RCCB Record Plus: FE160 and FE250 framesize
Rated at 160 and 250A, the FE frame sizes are designed for side-by-side mounting with FD63/160 types in panels. FE sizes are equipped with an easily accessible busbar connection and can also be supplied with cable lugs for use with copper or aluminum conductors. The design allows the use of interchangeable thermal-magnetic, magnetic-only, and electronic trip units.
In compliance with EN 60947, BS, VDE, UTE, KEMA, CEI.
- 3 and 4 pole versions available
- FE160 to 160A and FE250 to 250A
- Full range of add-on accessories, including:
- thermal magnetic/magnetic trip units
- auxiliary contacts
- completely integrated add-on devices available
- rotary handles
- electrical operators
- connectivity – 60 mm system
- Changeover/Power transfer systems
RCCB Record Plus: FD63/160 frame size
Rated at 160A, the FD63/160 frame size is designed for use in both a DIN-rail environment with modular equipment and in industrial applications. It is supplied with IPXXB terminals suitable for direct connection of one or two conductors totalling up to 95 mm² and is available as a thermal-magnetic breaker, a moulded case switch, and as a magnetic-only motor circuit protector.
The FD63/160 bridges the gap between residential miniature circuit breakers and industrial moulded case circuit breakers.
- In compliance with EN 60947, BS, VDE, UTE, KEMA, CEI
- 3 and 4 pole versions available
- FD63 to 63A and FD160 to 160A
- Full range of add-on accessories, including:
- thermal magnetic/magnetic trip units
- auxiliary contacts
- completely integrated add-on devices available
- rotary handles
- electrical operators
- connectivity – 60 mm system
RCCB Record Plus: FK800, 1250 and 1600 framesize
Rated at 800,1250 and 1600A, the FK frame sizes are designed for use with the FG400 and 630 frame sizes. The design uses electronic trips units available in a number of performance ranges and allowing a wide variety of setting options and groundfault protection. If needed thermal-magnetic and magnetic only trip units are also available.
The FK connection area features easy-to access busbar connections or cable lugs for use with single or multiple copper or aluminum conductors.
In compliance with EN 60947, BS, VDE, UTE, KEMA, CEI.
- 3 and 4 pole versions available
- FK800 to 800A, FK1250 to 1250A and FK1600 to 1600A
- Full range of add-on accessories, including:
- thermal magnetic/magnetic trip units
- auxiliary contacts
- completely integrated add-on devices available
- rotary handles
- electrical operators
- connectivity – 60 mm system
- Changeover/Power transfer systems
RCCB Record Plus: FG400 and FG630 framesize
Rated at 400 and 630A, the FG frame size includes all of the advanced features of the FD and FE frame sizes. The FG connection area features easy-to access busbar connections. Cable lugs for use with single or multiple copper or aluminum conductors are optionally available. The breaker is designed for use with interchangeable electronic units that can be easily adapted to multiple levels of protection.
In compliance with EN 60947, BS, VDE, UTE, KEMA, CEI.
- 3 and 4 pole versions available
- FG400 to 400A and FG630 to 630A
- Full range of add-on accessories, including:
- thermal magnetic/magnetic trip units
- auxiliary contacts
- completely integrated add-on devices available
- rotary handles
- electrical operators
- connectivity – 60 mm system
- Changeover/Power transfer systems
Red Spot Standard
- Ratings from 2 Amps to 1250 Amps
- Fully complies with the requirements of BS88 Parts 1 & 2 and the associated IEC269
- ASTA 20 certified performance to 80kA, generally at 660Vac
- ASTA certified at 40kA up to 460Vdc
- Suitable for use in motor circuits and have superior motor starting ability, the availability of extended motor range Fuse Links (gM) enhances this capability
- Used to provide certified Type 2 co-ordination to IEC947 together with the contactors and overload relays
- Approved by leading authorities, including Power Generation Companies and Ministry of Defence
Special Application Fuse Links – Time Delay
- Time delay Fuse Links are used in conjunction with circuit breaker overcurrent releases
- "XF" range is designed and manufactured in accordance with ESI 12-6 Time Fuse Links
- "XF" range should be used on all new installations
- Available in ratings from 3 Amps to 15 Amps
- "TLF" range is an old design of time delay Fuse Link
- "TLF" range should only be used for replacement purposes
- Available in ratings of 5 Amp, 7.5 Amp and 10 Amp
Special Application Fuse Links – Aircraft
- Range of lightweight, high performance Fuse Links for use in Aircraft
- Certified for categories of duty 250AC3 and 120DC3
- Comply with the requirements of BS 88 and BSG 176
- Current rating of "AS" range is 0.25 Amps to 20 Amps
- Available with ferrule termination or alternatively tag contact type (designated "AST")
- Current rating of "UA" range is 30 Amps to 300 Amps
- Motor circuit version also available (designated "UAM")
- Approved by the "Air Registration Board"
Special Application Fuse Links – Interservice(NATO/MOD)
- Special range of Fuse Links developed for the armed forces for general purpose applications
- Developed in accordance with DEF STAN 59-96
- Range is now classified under NATO stock numbers which are universally recognised
- Available as end contact (ferrule) & tag contact type in up to 5 body sizes
- Current ratings from 0.25 Amps to 200 Amp
- Voltage rating up to 440V ac and 230V dc 33kA
- For use in all types of ships with Lloyds certified equipment
Air Circuit Breaker : M-Pact Plus Frame 3 -Withdrawable
Pre-mounted into a self-contained ‘cassette’, this versatile circuit breaker can be inserted or withdrawn via sliding rails using a racking drive mechanism controlled by a racking handle. It provides three set positions:
- Disconnected / test / connected
Any attempt to withdraw the unit whilst in service will automatically trip the breaker (by the racking position safety mechanism).
It can be racked to the disconnected position with the cubicle door closed or open.
- Carriage position switch (optional)
- Shutters and padlocking facility
- Contact indication
- Termination: rear (horizontal/vertical)
- Automatic disconnect of secondary circuits
- Easy wiring of the control circuit contacts
- Carrying handles for easy of removing the circuit breaker from the cassette
Air Circuit Breaker : M-Pact Plus Frame 1 &2 – Withdrawable
Pre-mounted into a self-contained ‘cassette’ ; this versatile circuit breaker can be inserted or withdrawn via sliding rails using a racking drive mechanism controlled by a racking handle.
It provides three set positions : Disconnected/Test/Connected.
Any attempt to withdraw the unit whilst in service will automatically trip the breaker, either by the racking position safety mechanism or by the insertion of the racking handle. It can be racked to the disconnected position with the cubicle door closed or open.
- Compliance with IEC947-2, BSEN60947-2 & VDE0660 part 101 & 107
- ASTA, KEMA and LOVAG certification to IEC947-2 & BSEN60947-2
- Rated short circuit performance from 50 kA to 80 kA (Icu=Ics=Icw) @ 415v
- Nominal ratings from 400A to 4000A
- 2 Frame Sizes: Frame 1 (400A to 2500A), Frame 2 (400A to 4000A
- 3 and 4 pole available in both fixed and withdrawable pattern
- Common height and depth for complete range
- Common accessories designed for simple installation
- Built-in safety features provided as standard
- Superior circuit protection integral to MPRO relay including combination of unrestricted, restricted and standby earth fault
- Communications facility incorporating MODBUS protocol
- Auxiliary contacts 5 n/o + 3 n/c provided as standard
- Ingress Protection – IP20 secondary contacts and IP43 door seal provided as standard with enhanced IP54 door option available
- 2 or 3 way mechanical interlocking available in cable and rod design
- Fully insulated steel shutters with front access padlocking facility as standard
- Lifting lugs for ease of removal of the breaker from the ‘cassette’