People protection against the risk of electrocution and property protection against the risk of an electrical fire. Also with overcurrent protection.

 

  • In accordance with EN/IEC 61009-1
  • Recognized UL 1053, UL file E248309
  • Maximum voltage AC (V) 240 or 277
  • Fault current withstand (kA) 5 (277V), 10 (240V)
  • Thermal settings In (A) 10-32
  • Residual current IΔ n (mA) 10, 30, 100, 300
  • Tripping characteristic B-C
  • Selectivity class 3
  • Rated maximum voltage AC Un (V) 240
  • Minimum operating voltage U bmin (V) 100
  • Nuisance tripping resistance  250A 8/20μs;
                                                   200A 0,5μs-100kHz
  • Making and breaking capacity (EN/IEC 61009-1) Im = 6000A
  • Residual making and breaking capacity (EN/IEC 61009-1) Icn = 5000/10000A at 230V
  • Short-circuit capacity (EN/IEC 60947-2) Icu = 15000A at 230V
  • CEBEC and UR approval