Residual Current Circuit Breakers – RCBO’s DPA100 UL approval
People protection against the risk of electrocution and property protection against the risk of an electrical fire. Also with overcurrent protection.
- In accordance with EN/IEC 61009-1
- Recognized UL 1053, UL file E248309
- Maximum voltage AC (V) 240 or 277
- Fault current withstand (kA) 5 (277V), 10 (240V)
- Thermal settings In (A) 10-32
- Residual current IΔ n (mA) 10, 30, 100, 300
- Tripping characteristic B-C
- Selectivity class 3
- Rated maximum voltage AC Un (V) 240
- Minimum operating voltage U bmin (V) 100
- Nuisance tripping resistance 250A 8/20μs;
200A 0,5μs-100kHz - Making and breaking capacity (EN/IEC 61009-1) Im = 6000A
- Residual making and breaking capacity (EN/IEC 61009-1) Icn = 5000/10000A at 230V
- Short-circuit capacity (EN/IEC 60947-2) Icu = 15000A at 230V
- CEBEC and UR approval